The ESI data ingested by github.com/linuxcnc-ethercat/esi-data describes 2 revision(s) of this hardware. Here are the known revisions and their differences.
This also includes the send and receive PDOs defined for each revision, and a link to other known devices with identical PDOs.
Revision | r16 |
r17 |
|
Name | ELX3181 1Ch. Ana. Input 4-20mA, HART, Ex i |
||
PID | 0x970bc4d9 |
||
Revision Code | 0x00100000 |
0x00110000 |
|
Equivalant Devices | |||
TX PDOs | 0x1a00: AI Standard |
||
0x6000:01 Status__Underrange BOOL |
|||
0x6000:02 Status__Overrange BOOL |
|||
0x6000:03 Status__Limit 1 BIT2 (2 bits) |
|||
0x6000:05 Status__Limit 2 BIT2 (2 bits) |
|||
0x6000:07 Status__Error BOOL |
|||
0x6000:0e Status__Sync error BOOL |
|||
0x6000:0f Status__TxPDO State BOOL |
|||
0x6000:10 Status__TxPDO Toggle BOOL |
|||
0x6000:11 Value INT (16 bits) |
|||
0x1a01: AI Compact |
|||
0x6000:11 Value INT (16 bits) |
|||
0x1a10: HART Cmd3 |
|||
0x6080:01 Field Device Status USINT (8 bits) |
|||
0x6080:02 Cyclic Frame Cnt USINT (8 bits) |
|||
0x6080:05 Primary Variable Units Code USINT (8 bits) |
|||
0x6080:06 Secondary Variable Units Code USINT (8 bits) |
|||
0x6080:07 Tertiary Variable Units Code USINT (8 bits) |
|||
0x6080:08 Quaternary Variable Units Code USINT (8 bits) |
|||
0x6080:09 Primary Variable Loop Current REAL (32 bits) |
|||
0x6080:0a Primary Variable REAL (32 bits) |
|||
0x6080:0b Secondary Variable REAL (32 bits) |
|||
0x6080:0c Tertiary Variable REAL (32 bits) |
|||
0x6080:0d Quaternary Variable REAL (32 bits) |